The auxiliary switch block is integrated, saving a slot on the rail.
Auxiliary contact ratings and switching frequency
The auxiliary contacts carry 10 A at 24 V, 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. These are the rated values for the integrated auxiliary switch — check your control circuit voltage against these curves. Switching frequency limits: 1 000 operations/hour at AC-1, 750/h at AC-2, AC-3, and AC-3e, and 250/h at AC-4. For high-cycle applications like rapid reversing, stay within the AC-4 ceiling.
Wiring and clearances
Terminals accept solid or stranded wire from 0.5 to 4 mm², with dual-wire capacity: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². Minimum clearances to adjacent components: 10 mm upward, forward, and downward; 6 mm at the sides.
This order code is at a current-production lifecycle stage. No official successor has been issued.