SIRIUS power contactor for panel integration
The coil is 24 V DC with screw-type terminals; auxiliary switch included.
Switching duty and mechanical life
Rated for AC-3 motor switching at 750 operations per hour maximum, AC-1 resistive load at 1000 ops/h, and AC-4 inching/jogging at 250 ops/h. Auxiliary contact ratings: 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.2 A at 440 V.
Mounting and wiring clearances
Wire cross-section: solid or stranded 0.5–4 mm²; dual-wire capacity up to 2x 4 mm².