Skip to main content
Siemens 3RT2017-1AV02 — Contactors

Siemens 3RT2017-1AV02 SIRIUS Power Contactor, Size S00, 24 V

MPN3RT2017-1AV02
Active

Siemens SIRIUS power contactor, size S00, 24 VDC coil, screw terminals, 45 mm width, 73 mm depth, snap-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2017-1AV02 — Identification
ParameterValue
Contactor frame sizeS00
3RT2017-1AV02 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V2 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2017-1AV02 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz400 V
3RT2017-1AV02 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2017-1AV02 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2017-1AV02 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2017-1AV02 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2017-1AV02 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2017-1AV02 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm
3RT2017-1AV02 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

The 24 VDC coil with screw-type terminals is the primary ordering distinction for this variant.

Rated operational current in AC-3 duty (motor switching) is the headline figure: at 400 V, the contactor is rated for 3 A, and at 230 V it carries a 2 hp motor load. AC-3 switching frequency maxes out at 750 operations per hour, while AC-4 (plugging/reversing) is limited to 250 per hour. Mechanical life is typical 30,000,000 operations, meaning the contactor outlasts most panel builds before a wear-out replacement.

DIN rail and panel integration

Width is 45 mm, depth 73 mm, height 58 mm. Wire terminations accept solid or stranded conductors from 0.5 to 4 mm², with dual-wire capability (2x 0.5...1.5 mm², 2x 0.75...2.5 mm², or 2x 4 mm²). The screw terminals on the magnet coil match the main contact termination style, simplifying the wireman's kit.

Frequently asked questions

What are the key dimensions for panel layout?

Width 45 mm, depth 73 mm, height 58 mm. Clearances: 10 mm up/down/forward, 6 mm at sides.

What wire sizes does the contactor accept?

Solid or stranded from 0.5 to 4 mm². Dual-wire capability: 2x 0.5...1.5 mm², 2x 0.75...2.5 mm², or 2x 4 mm².

What compliance documentation is available?

RoHS, REACH, UL, and IEC declarations are provided by Siemens for this part.

MPN
3RT2017-1AV02