Skip to main content
Siemens 3RT2017-2AH01 — Contactors

Siemens 3RT2017-2AH01 SIRIUS Power Contactor, 24 VDC Coil, 1

MPN3RT2017-2AH01
Active

Siemens SIRIUS, power contactor, 3RT2017-2AH01, size S00, 24 VDC coil, 10 A rated, spring-type terminals, 45 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2017-2AH01 — Identification
ParameterValue
Contactor frame sizeS00
3RT2017-2AH01 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V2 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2017-2AH01 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz48 V
3RT2017-2AH01 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2017-2AH01 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2017-2AH01 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2017-2AH01 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2017-2AH01 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2017-2AH01 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RT2017-2AH01 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

The size S00 frame keeps it compact at 45 mm wide, 70 mm high, and 73 mm deep, fitting standard 35 mm DIN rail per DIN EN 60715 via screw or snap-on mounting.

The 10 A rating at 24 VDC is the continuous current the main contacts can carry in DC control circuits. For motor switching, the AC-3 duty cycle is rated at 750 operations per hour maximum, which suits moderate-speed conveyor or pump cycling. The AC-4 rating drops to 250 operations per hour, reflecting the higher electrical stress of inching or plugging duty. Mechanical service life is typical at 30 million operations, meaning the contactor body itself will outlast most application cycles before wear. These are minimum air gaps for heat dissipation and arc containment — plan your DIN rail layout accordingly.

Spring-type terminals on the coil and main contacts accept 0.5 to 4 mm² solid or stranded wire, or 2x (0.5 to 4 mm²) for looping.

Frequently asked questions

What is the closest functional alternative to the 3RT2017-2AH01?

The 3RT2024-2BB40 is a peer in the same SIRIUS family, but it has a different coil voltage and contact rating. Verify your control voltage and load current before substituting — the 3RT2017-2AH01 is a 24 VDC coil, 10 A rated contactor, while the 3RT2024-2BB40 uses a different coil and may have a different frame size.

What are the key dimensions of the 3RT2017-2AH01?

Width is 45 mm, height is 70 mm, and depth is 73 mm. These dimensions fit the size S00 frame.

What wire sizes does the 3RT2017-2AH01 accept?

Solid or stranded wire from 0.5 to 4 mm², or 2x (0.5 to 4 mm²) for looping. The coil connection uses spring-type terminals.

Will the 3RT2017-2AH01 drop into a panel specified for the 3RT2024-2BB40?

Both are size S00 contactors on the same DIN rail footprint, so mechanical fit is the same. However, the coil voltage and contact ratings differ — the 3RT2017-2AH01 uses a 24 VDC coil rated at 10 A, while the 3RT2024-2BB40 has different specs. Check your control circuit voltage and load current before swapping.

MPN
3RT2017-2AH01