The size S00 frame keeps it compact at 45 mm wide, 70 mm high, and 73 mm deep, fitting standard 35 mm DIN rail per DIN EN 60715 via screw or snap-on mounting.
The 10 A rating at 24 VDC is the continuous current the main contacts can carry in DC control circuits. For motor switching, the AC-3 duty cycle is rated at 750 operations per hour maximum, which suits moderate-speed conveyor or pump cycling. The AC-4 rating drops to 250 operations per hour, reflecting the higher electrical stress of inching or plugging duty. Mechanical service life is typical at 30 million operations, meaning the contactor body itself will outlast most application cycles before wear. These are minimum air gaps for heat dissipation and arc containment — plan your DIN rail layout accordingly.
Spring-type terminals on the coil and main contacts accept 0.5 to 4 mm² solid or stranded wire, or 2x (0.5 to 4 mm²) for looping.