Core identity and fit
It uses spring-type terminals for the magnet coil connection, accepting solid or stranded conductors from 0.5 to 4 mm², and mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715.
The auxiliary contact block on this contactor is rated for 10 A at 24 V, dropping to 0.2 A at 440 V — that's the switching capacity across the voltage range, not the continuous carry current. For motor duty, the contactor is specified for 750 operations per hour at AC-3 and AC-3e, and 250 at AC-4, which governs jogging or reversing applications. The main contacts have a mechanical life of 30 million operations, meaning the coil and armature outlast the arc erosion on the contacts in a well-sized application.
Thermal and mounting constraints
Switching performance and losses
Maximum switching frequency varies by duty: 1000 ops/h at AC-1 (resistive), 750 at AC-2 and AC-3, and 250 at AC-4.