Standing mount on a horizontal surface is the specified position. The contactor carries an auxiliary switch and is rated for main contacts in the 20 to 12 A range. It is currently in its active lifecycle stage.
The spring terminals accept solid or stranded wire from 0.5 to 4 mm², or 2x (0.5 to 4 mm²) for daisy-chaining. Dimensions are 73 mm deep, 45 mm wide, 70 mm high — fits a standard S00 slot in a panel layout.
Switching frequency and contact ratings
Maximum switching frequency depends on the duty class: 1,000 operations per hour at AC-1, 750/h at AC-2 and AC-3, 250/h at AC-4, and 750/h at AC-3e. The auxiliary contact ratings are defined per voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. Mechanical life is typical 30 million operations.
This part is in its current lifecycle stage — no discontinuation or phase-out has been announced.