Integrator note
It snaps onto 35 mm DIN rail per DIN EN 60715 and accepts solid or stranded wire from 0.5 to 4 mm² — two conductors per clamp if needed. The 45 mm width and 73 mm depth fit standard panel layouts; clearances of 10 mm upward, 10 mm forward, and 6 mm to the side keep heat dissipation predictable at rated loads.
Switching duty and mechanical life
Coil pick-up and drop-out timing: arcing time 10–15 ms, DC dropout 7–13 ms.
The integrated auxiliary switch handles 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. Motor load at 230 V is rated 2 hp.