It carries a 24 VDC coil rated at 10 A, with spring-type terminals that accept 0.5 to 4 mm² solid or stranded wire — no screw torque to verify, just strip and push. The 45 mm wide body snaps onto a 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface plus +/-22.5° tilt forward and backward, so it fits into tight panel layouts without reworking the backplate.
The 24 VDC coil draws its rated current at 24 V and drops out cleanly below the undervoltage threshold — standard for PLC-driven 24 V control buses. The main contacts are rated 10 A at 24 VDC, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V, so the DC switching capability scales inversely with voltage as you'd expect for a contactor this size.