The coil holds at 24 VDC nominal; dropout occurs below the pick-up threshold, so verify your control supply stays above that during brownout conditions.
Mounting and Clearance — DIN Rail Fit
The contactor measures 45 mm wide by 70 mm tall by 73 mm deep — a compact S00 footprint that leaves room alongside overload relays and busbars. Standing mounting position on a horizontal surface is specified; derate if you must mount on its side.
Switching Ratings and Mechanical Life
Rated operational current at 24 V is 10 A; at 400 V it is 3 A. The contactor is also rated for 2 hp at 230 V. For AC-4 duty (plugging / inching) the maximum switching frequency drops to 250 1/h; stay within that for severe switching applications.
Terminal Capacity and Auxiliary Contacts
Spring-type terminals accept solid or stranded conductors from 0.5 to 4 mm², or 2x (0.5 to 4 mm²) for looping through.