It's rated for 20 A on the main contacts and handles switching frequencies up to 1000 cycles per hour under AC-1 resistive loads, 750 under AC-3 motor duty.
Spring-type terminals accept solid or stranded wire from 0.5 to 4 mm², or 2x (0.5 to 4 mm²) for paralleled feeds. The auxiliary contacts (no built-in auxiliary switch on this variant) have DC switching ratings: 6 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. DC dropout time is 38 to 65 ms.