It uses spring-type terminals accepting 0.5 to 4 mm² solid or stranded wire, and mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715.
Duty ratings and switching frequency
Main contact rated current spans 20 A down to 12 A depending on duty. Maximum switching frequency varies by load: 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting/running), and 250/h at AC-4 (plugging/inching). The AC-3e rating also allows 750/h. For a 24 VDC coil, pick-up and drop-out times run 38 to 65 ms, with arcing time of 10 to 15 ms.
The size S00 frame keeps the contactor compact for dense panel layouts.