DC switching capacity and coil characteristics
The 3RT2017-2SB42: The 24 VDC coil has a pickup range of 0.85 to 1.85 times rated value, meaning it reliably pulls in at 20.4 V and stays sealed up to 44.4 V.
Switching frequency and mechanical endurance
Maximum switching rates are 1000 cycles/hour for AC-1 resistive loads, 750 cycles/hour for AC-2 and AC-3 motor loads, and 250 cycles/hour for AC-4 plugging/inching duty.
Panel fit and clearance requirements
Dimensions are 45 mm wide, 70 mm tall, and 73 mm deep — the S00 frame fits tightly in a crowded DIN rail section.