DIN rail fit and panel clearances
The 45 mm width and 58 mm height keep it to a single 1.8-inch module footprint.
Auxiliary contact ratings and switching capability
Built-in auxiliary switch handles pilot duty across a wide voltage range: 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 230 V, 3 A at 400 V, 0.2 A at 440 V, 11 A at 480 V, and 2 A at 500 V. At 230 V it also carries a 2 hp motor load. These cover most PLC input and relay coil switching needs without an add-on block.
Switching frequency and mechanical endurance
Rated for 1 000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2, AC-3, and AC-3e, and 250 cycles/hour at AC-4. Typical mechanical life is 30 000 000 operations — this is a long-service part for frequent cycling applications like conveyor or pump control.
Coil connection and environmental range
Magnet coil termination uses a ring cable lug connection — factor that into wiring prep.
Marked as current production stage. This is a standard-catalog SIRIUS contactor, widely specified in new panels and as a replacement for installed S00-frame equipment.