Skip to main content
Siemens 3RT2018-1AP02 — Contactors

Siemens SIRIUS 3RT2018-1AP02 Power Contactor, Size S00, 24 V

MPN3RT2018-1AP02
Active

Siemens SIRIUS 3RT2018-1AP02 power contactor, size S00, 24 VDC coil, screw-type terminals, screw and snap-on mounting onto 35 mm DIN rail.

$26.67Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2018-1AP02 — Identification
ParameterValue
Contactor frame sizeS00
3RT2018-1AP02 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V11.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V2 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2018-1AP02 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT2018-1AP02 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2018-1AP02 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 50A (690V,100kA), aM: 25A (690V,100kA), BS88: 50A (415V,80kA)
Short-circuit coordination type 2, fusegG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2018-1AP02 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2018-1AP02 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2018-1AP02 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2018-1AP02 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm
3RT2018-1AP02 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

The Siemens SIRIUS 3RT2018-1AP02 is a size S00 power contactor with a 24 VDC coil, designed for screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715. It carries an auxiliary switch and is rated for 10 A at 24 V on the auxiliary contacts, with a mechanical service life of 30,000,000 operating cycles typical.

Duty Class and Switching Frequency

Switching frequency is duty-dependent: 1,000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2 and AC-3 (motor starting/running), and 250 cycles/hour at AC-4 (plugging/inching). The AC-3e rating also permits 750 cycles/hour. These limits govern the thermal load on the contactor in repetitive switching applications.

Coil and main contact terminals are screw-type. Conductor cross-sections accepted: solid or stranded 0.5 to 4 mm², or two conductors per terminal: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². Main contact torque range is 20 to 12 (units implied as Nm or in-lbs per standard practice).

Auxiliary contact current ratings vary with voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. Motor rating at 230 V is 2 hp.

Frequently asked questions

What are the key dimensions of the 3RT2018-1AP02?

Width is 45 mm, height is 58 mm, and depth is 73 mm.

What conductor sizes does the 3RT2018-1AP02 accept?

Solid or stranded conductors from 0.5 to 4 mm² are accepted, with options for two conductors per terminal.

What is the coil power consumption of the 3RT2018-1AP02?

Coil power consumption is 0.25 A at both 50 Hz and 60 Hz.

What are the operating and arcing times for the 3RT2018-1AP02?

Operating time at AC is 4 to 15 ms. Arcing time is 10 to 15 ms.

MPN
3RT2018-1AP02