SIRIUS size S00 contactor, 24 VDC coil, spring terminals
Wiring and mounting constraints
Mounting position: ±180° rotation on vertical surface, tilt ±22.5°. Clearances: 10 mm up, 10 mm forward, 10 mm down, 6 mm sides.
Duty-cycle ratings and mechanical life
Switching frequency depends on the duty class. AC-1 (resistive loads) allows up to 1 000 1/h. AC-2 and AC-3 (motor starting, slip-ring motors) are rated at 750 1/h. AC-4 (plugging, inching) drops to 250 1/h. AC-3e (enhanced motor rating) also permits 750 1/h. Mechanical life is typical at 30 000 000 operations — that's the contactor body, not the contacts under load. Arcing time runs 10 to 15 ms.