The 45 mm width and 97 mm depth fit standard S0 footprints, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward/backward — useful when you're squeezing it into a crowded enclosure.
The auxiliary contact block is rated for 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.6 A at 440 V — so it handles control-circuit loads across common DC and AC voltages without an extra interface relay. The main contact wiring accepts solid or stranded conductors from 1 to 10 mm², and for fine-stranded wire you can double up: 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). That covers most panel-building terminations without needing lugs. Mechanical life is rated at 10 000 000 operations typical, and the maximum switching frequency hits 1 000 operations per hour under AC-1, AC-2, AC-3, and AC-3e duty, dropping to 300 ops/h under AC-4. That means this contactor is comfortable cycling a motor start/stop every 3.6 seconds in AC-3 service, but heavy inching or plugging (AC-4) needs a slower rhythm — one cycle every 12 seconds.