3RT2023-1AP04-ZX95
CONTACTOR, AC-3, 4KW/400V, 2NO+2NC, AC 230V 50HZ, 3-POLE, SZ S0 SCREW TERMINAL REMOVABLE AUX. SWITCH PACKAGE = 48 UNITS
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S0 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 8.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 1 hp |
| Rated value @ 24 V | 6 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC |
| Rated value @ 50 Hz | 0.25 |
| Rated value @ 50 Hz | 230 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 63A (690V,100kA), aM: 32A (690V,100kA), BS88: 63A (415V,80kA) |
| Short-circuit coordination type 2, fuse | gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | screw-type terminals |
| Aux. / control circuit connection | screw-type terminals |
| Conductor cross-section, solid | 1 ... 10 mm² |
| Conductor cross-section, solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 10 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 85 mm |
| Depth | 141 mm |
| Parameter | Value |
|---|---|
| At AC | 4 ... 16 ms |
Frequently asked questions
What does the -ZX95 suffix mean on a Siemens 3RT2023-1AP04 contactor?
Buyers must confirm the ZX95 variant matches their required auxiliary contact configuration before purchase.
Is the 3RT2023-1AP04-ZX95 still in active production?
Product lifecycle status determines whether the part is safe to specify in new designs or only available as a spare.
What coil voltage does the Siemens 3RT2023-1AP04-ZX95 use?
Wrong coil voltage is the most common ordering error; must verify 230V 50Hz matches control circuit design.
What is the equivalent or replacement for 3RT2023-1AP04-ZX95?
Needed when stock is unavailable or for cross-referencing during MRO spares planning.
Where can I buy the 3RT2023-1AP04-ZX95 in the 48-unit pack from an authorized distributor?
Ensures genuine product and warranty coverage for high-volume panel builders.
Where can I download the datasheet PDF for 3RT2023-1AP04-ZX95?
Datasheet confirms AC-3 rating, terminal type, and dimensions needed for panel layout and UL compliance.