SIRIUS Size S0 power contactor — 48 VDC coil, screw terminals
Rated operational currents: 10 A at 24 V DC, 2 A at 48 V DC, 2 A at 60 V DC, 1 A at 110 V DC, 0.9 A at 125 V DC, 0.3 A at 220 V DC, and 3 A at 400 V AC. The AC-3 switching frequency is rated up to 1 000 operations per hour; AC-4 is limited to 300 per hour. The contactor includes an auxiliary switch and accepts main contact wire sizes from 16 to 8 AWG (solid or stranded 1 … 10 mm²).
Width is 45 mm, height 85 mm, depth 107 mm. Coil pick-up is at 0.8 of rated voltage, drop-out at 1.1 of rated voltage (full-scale value). Wire sizes: solid or stranded 1 … 10 mm² for main contacts; auxiliary contacts accept 2x (0.5 … 1.5 mm²) or 2x (0.75 … 2.5 mm²). Arcing time is 10 ms; DC switching time is 15 … 18 ms.