Panel Integration and Fit
Its 45 mm width, 102 mm height, and 97 mm depth fit standard panel layouts, with a mounting position that allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward and backward. The spring-type terminals on the magnet coil accept solid or stranded conductors from 1 to 10 mm², and dual conductors from 0.5 to 2.5 mm², so it integrates directly into a control cabinet without needing lug adapters.
Duty Cycle and Switching Performance
This contactor is rated for 1,000 operating cycles per hour under AC-1, AC-2, AC-3, and AC-3e duty, and 300 cycles per hour under AC-4. The arcing time is 10 ms. For auxiliary contact switching, the 24 V rated value is 10 A, with derated values at higher voltages (2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.6 A at 440 V). The typical mechanical service life of the contactor is 10,000,000 operations.