The 24 VDC coil draws a rated operating current of 6 A, with a pickup threshold of 0.8 x rated voltage and a dropout below that. Spring-type terminals accept solid or stranded conductors from 1 to 10 mm², with dual-wire capability for 2x (0.5 to 2.5 mm²).
Coil and switching ratings
Coil ratings at 24 VDC: 6 A. At higher DC voltages the current drops — 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. The AC-3 motor switching rating supports up to 1 000 operating cycles per hour, while AC-4 (inching/jogging) is limited to 300 cycles per hour. Mechanical life is typical 10 000 000 operations.
The Size S0 footprint (45 mm wide, 102 mm tall, 154 mm deep) fits standard DIN-rail enclosures. Spring terminals reduce wiring time versus screw terminals — strip length for solid/stranded is 10 mm. No special tooling needed beyond a screwdriver for the spring release.