SIRIUS S0 power contactor — 3RT2023-4AK60
Panel fit: 45 mm wide, 85 mm high, 97 mm deep. Side clearance to adjacent devices is 6 mm; forward and upward clearance 10 mm.
Rated for 1000 switching cycles per hour in AC-1, AC-2, AC-3, and AC-3e duty; AC-4 max is 300 cycles/h. That 1000 cycles/h covers most motor-starting and resistive-load applications; AC-4 (plugging/inching) is the limiting case. Auxiliary contact switching capacity (24 V rated value: 10 A; 48 V: 2 A; 60 V: 2 A; 110 V: 1 A; 125 V: 0.9 A; 220 V: 0.3 A; 400 V: 3 A; 440 V: 0.6 A; 480 V: 7.6 A; 500 V: 2 A). These are the make/break ratings for the built-in auxiliary switch — use them for control-circuit isolation, not main power. Mechanical endurance typical: 10 million operations. Coil connection is ring cable lug.