The DC-operated coil uses a ring cable lug connection, which is a specific termination style for the magnet coil — not a standard screw terminal. This matters for panel wiring: you need a ring terminal crimped to the coil leads, not a ferrule or bare wire. The 45 mm width means it fits the standard S0 footprint — no surprises in an existing panel layout.
Integration notes
The S0 frame size is a workhorse form factor for up to about 7.5 kW motor loads at 400 V AC-3 duty. The dimensions — 45 mm wide, 91 mm high, 107 mm deep — are the standard S0 envelope, so it fits existing panel cutouts and busbar layouts without rework. The ring cable lug connection on the coil is the key wiring detail. Standard contactors often use blade or screw-clamp terminals; this one expects a ring terminal bolted to the coil posts. Verify your control wiring ends match before committing the panel — a field change from ring to fork terminal isn't possible without adapter hardware.