Product Identification and Key Ratings
Per the datasheet, the contactor is rated for a mechanical service life of 10,000,000 operating cycles, and its main contacts accept solid or stranded conductors from 1 to 10 mm². The headline switching capacity is defined by the rated operational currents: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.6 A at 440 V. For motor loads at 230 V, it is rated for 2 hp. These values define the contactor's capability across common control and distribution voltages — the 400 V rating of 3 A, for example, confirms it can switch a small three-phase motor or a resistive heater bank at that voltage level. The contactor supports a maximum switching frequency of 1,000 operating cycles per hour under AC-1, AC-2, AC-3, and AC-3e duty, and 300 cycles per hour under AC-4 duty. The arcing time is specified as 10 ms at AC. These figures matter for applications with frequent start/stop cycles — AC-4 duty (plugging or inching) is the most demanding, and the lower 300 cycles/h limit reflects the increased contact wear under those conditions.
Its dimensions are 85 mm height, 45 mm width, and 97 mm depth — the S0 frame size fits into the common panel layout alongside other S0 components. These clearances must be maintained inside the panel to avoid thermal derating or arc flash to adjacent components. The auxiliary contact terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded conductors. The coil terminal type is screw-type, consistent with the main terminals.