The contactor accepts solid or stranded conductors from 1 to 10 mm² on the main circuit, and the auxiliary wiring can take 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²).
Dimensions and Clearances
At 85 mm high, 45 mm wide, and 141 mm deep, this contactor fits the standard S0 footprint. That 6 mm side gap is the tightest constraint — adjacent devices on the rail need that spacing for heat dissipation and arc containment.
Switching Performance and Mechanical Life
Rated for 1,000 operating cycles per hour under AC-1, AC-2, AC-3, and AC-3e duty, dropping to 300 cycles per hour under the heavier AC-4 category. Arcing time is a tight 10 ms window, and the make/break times at AC sit between 4 and 16 ms.