It mounts on 35 mm DIN rail per DIN EN 60715, with screw and snap-on fastening, and can be rotated ±180° on a vertical surface or tilted ±22.5° forward/backward, giving you flexibility in tight enclosures. The coil uses spring-type terminals, rated 24 VDC, and the auxiliary contacts are rated 10 A at 24 V, 2 hp at 230 V, and 3 A at 400 V — solid for signaling back to a PLC or driving a pilot light.
Integration Notes
Wire the main contacts with solid or stranded copper from 1 to 10 mm²; auxiliary contacts accept 2x (0.5 to 2.5 mm²). The spring-type coil terminals are tool-less — just push in the stripped wire. Clearance around the contactor: 10 mm above and below, 6 mm to the side. The arcing time is 10 ms, so keep that in mind for coordination with upstream protection.
Duty Ratings
Rated for 1 000 operations per hour in AC-1, AC-2, AC-3, and AC-3e duty; AC-4 drops to 300 operations per hour.