It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, fitting a 45 mm wide footprint with a depth of 97 mm and height of 102 mm. An auxiliary switch is built in, rated for 10 A at 24 V and derating to 0.3 A at 220 V — enough for signaling back to a PLC or status lamp without an extra block.
Spring-type terminals accept solid or stranded wire from 1 to 10 mm², or two conductors of 0.5 to 2.5 mm² each. No screw torque to check — just strip and insert — which speeds wiring on repetitive builds.
Duty cycle and thermal limits
Rated for 1,000 switching operations per hour in AC-1, AC-2, AC-3, and AC-3e duty; AC-4 drops to 300 operations per hour due to the heavier electrical wear from inching and plugging cycles.