Integrator note — SIRIUS 3RT2024-2KB40 coupling contactor
Rated DC-1 switching at 24 V carries 10 A; at 48 V and 60 V the rating drops to 2 A, and at 220 V to 0.3 A — so for higher-voltage DC loads the contactor is limited to signal-level currents, not power switching. The coil draws an initial inrush of 1.25 A and holds at 0.7 A; arcing time is 10 ms, and the mechanical life is rated at 10 million operations typical.
Spring-type terminals accept solid or stranded conductors from 1 to 10 mm², or 2x (0.5 to 2.5 mm²) for daisy-chaining. Main contacts are sized for 18 to 8 AWG — verify your wire gauge fits the terminal range before terminating.