Integrator's quick-fit check
The auxiliary block is built in — 1 NO + 1 NC — rated 10 A at 24 V, 2 A at 48 V or 60 V, and 1 A at 110 V. Mounting is screw or snap-on onto 35 mm DIN rail per DIN EN 60715; the S0 footprint is 45 mm wide, 102 mm tall, 107 mm deep. Clearance: 10 mm upward, downward, and forward; 6 mm at the sides.
Duty class and switching frequency
Rated for 1,000 switching cycles per hour in AC-1 (resistive), AC-2 (slip-ring motor), AC-3 (squirrel-cage motor start/run), and AC-3e (enhanced AC-3) duty. AC-4 (inching/plugging) is limited to 300 cycles per hour — the higher arc energy in reversing or jogging applications demands the derate. Mechanical lifetime is 10 million operations typical; main contact electrical life is 18 to 8 million depending on load.
Power dissipation at 50 Hz is 0.51 W, at 60 Hz 0.56 W — negligible for panel heat budgeting. Inrush current peak is 25 A. Operate factor 0.7, release factor 1.1 — the coil holds reliably across the full voltage tolerance.