Integrator's note — SIRIUS 3RT2025-1AK60-ZX95
Coil voltage is 24 V rated value, pulling in at 10 A at 24 V and rated for 3 hp at 230 V. Mounting is via screw and snap-on onto a 35 mm DIN rail per DIN EN 60715, with +/-180° rotation possible on a vertical surface and +/-22.5° tilt forward/backward — useful for tight enclosures where orientation flexibility matters.
DIN rail integration and panel fit
The S0 contactor measures 45 mm wide, 85 mm high, and 97 mm deep — a compact footprint that fits standard 35 mm DIN-rail enclosures. Wiring accepts solid or stranded conductors from 1 to 10 mm², with dual-wire capacity for 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). Clearance spacing: 10 mm upwards, downwards, and forwards; 6 mm at the side.
Key electrical ratings and their meaning
At AC-1 (resistive load) maximum switching frequency is 1,000 cycles per hour; same for AC-2 and AC-3 motor duty. AC-4 (plugging/reversing) drops to 300 cycles per hour — this is the limiting factor for applications with frequent inching or reversing. Rated operational current at 24 V is 10 A; at 48 V and 60 V it drops to 2 A; at 400 V it is 3 A. The 3 hp rating at 230 V tells you this contactor is sized for small-to-medium motor loads on single-phase or three-phase 230 V systems.