For motor duty, the contactor is rated at 3 hp at 230 V and 14 A at 480 V — these are the AC-3 switching figures that govern real motor starts. The auxiliary contact ratings drop as voltage rises: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. Switching frequency is rated at 1 000 operating cycles per hour for AC-1, AC-2, AC-3, and AC-3e duty, dropping to 300 cycles per hour for AC-4 (plugging/reversing).
Integration and clearances
The contactor occupies a single 45 mm slot on the DIN rail — standard for S0 frame size. Screw terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) for auxiliary wiring.