The 24 VDC coil pulls in at 0.8 of rated voltage (about 19.2 V) and drops out with a 15–18 ms delay, which is fast enough for most interlocking circuits but not a safety-rated instant drop. The main contacts are rated for AC-1 resistive loads up to the contactor's full thermal current and AC-3 motor switching at 400 V at 3 A — that's roughly a 1.1 kW motor at 400 V three-phase. AC-4 (inching/jogging) is limited to 300 operations per hour versus 1 000 for AC-3, so if your application cycles the contactor under load repeatedly, this part is not the right choice; you'd want a higher-rated frame or a dedicated reversing pair. Wire range accepts 1–10 mm² solid or stranded on the main contacts, with auxiliary terminals taking 2x 0.5–1.5 mm² or 2x 0.75–2.5 mm². That covers most control wiring up to 10 AWG solid. The screw-type terminals are standard for panel builders — no special tooling needed. The mounting position allows ±180° rotation on a vertical surface and ±22.5° tilt forward/backward, which gives flexibility in tight enclosures but keep the arcing clearance of 10 mm upwards and 6 mm sideways per the spec.

Siemens 3RT2025-1BA40 SIRIUS Power Contactor, Size S0, 24 VD
Siemens SIRIUS power contactor, Size S0, 3RT2025-1BA40, 24 VDC coil, screw-type terminals, screw and snap-on mounting on 35 mm DIN rail (EN 60715), 45 mm width.
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S0 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 15.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 3 hp |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | DC |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 63A (690V,100kA), aM: 32A (690V,100kA), BS88: 63A (415V,80kA) |
| Short-circuit coordination type 2, fuse | gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | screw-type terminals |
| Aux. / control circuit connection | screw-type terminals |
| Conductor cross-section, solid | 1 ... 10 mm² |
| Conductor cross-section, solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 10 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 85 mm |
| Depth | 107 mm |
Product details
Frequently asked questions
How do I get current pricing and availability for 3RT2025-1BA40?
Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.
What is 3RT2025-1BA40's listed depth?
The depth is 107 mm, with a width of 45 mm and height of 85 mm.
What wire sizes does the 3RT2025-1BA40 accept?
Main contacts accept 1–10 mm² solid or stranded. Auxiliary terminals accept 2x 0.5–1.5 mm² or 2x 0.75–2.5 mm².
Will 3RT2025-1BA40 drop into a panel specified around 3RT2015-1BW42 without rewiring?
Both are Size S0 contactors on the same 45 mm DIN-rail footprint, so the mechanical swap is straightforward. Verify the coil voltage — the 3RT2025-1BA40 uses a 24 VDC coil — and confirm the auxiliary contact configuration matches your circuit, as the 3RT2015-1BW42 may carry a different auxiliary block.