S0 frame, 45 mm wide — panel fit
The 3RT2025-2AB00: Depth is 97 mm, height 102 mm, so it clears most 120 mm deep enclosures without forcing a deeper gland plate.
Coil termination and auxiliary contact ratings
The magnet coil uses spring-type terminals (push-in or cage-clamp style), not screw clamps — this speeds wiring and resists loosening under vibration. An auxiliary switch is built in.
Switching frequency and thermal limits
Rated for 1,000 operating cycles per hour in AC-1, AC-2, AC-3, and AC-3e duty — that is one cycle every 3.6 seconds, which covers most conveyor and pump cycling rates. In AC-4 (plugging/inching) the limit drops to 300 ops/h, so high-duty jogging applications need to stay under that ceiling. The 60 °C ceiling is typical for panel interiors near drives or transformers — if the enclosure ambient exceeds that, derate or add ventilation.