DIN-rail footprint and panel clearance
Depth is 97 mm, height 102 mm. That 6 mm side gap is tighter than the 10 mm on other axes — when packing multiple contactors side-by-side, that's the dimension to watch for heat dissipation and wiring access.
Wire termination and operating cycle limits
Main circuit terminals accept solid or stranded wire from 1 to 10 mm², and up to 2x (0.5 to 2.5 mm²) for the auxiliary circuit. Maximum operating cycles per hour: 1,000 for AC-1, AC-2, AC-3, and AC-3e duty; drops to 300 for AC-4 (plugging/reversing).