The 24 VDC coil pulls in at 10 A inrush per the datasheet, holding steady at the rated voltage.
Duty ratings and switching frequency
AC-3 motor switching is rated at 21 A at 480 V, which covers most 10–15 hp three-phase induction motors in that voltage class. AC-1 resistive load rating reaches 40 A at 400 V. Maximum switching frequency varies by duty: 1000 cycles/hour for AC-1, 750 cycles/hour for AC-2 and AC-3, and 250 cycles/hour for AC-4 (plugging or inching). The AC-3e rating matches the standard AC-3 figure at 750 cycles/hour.
The S0 frame occupies 45 mm width on the rail.