This is the part for switching motor loads or resistive loads in a control panel where the coil voltage is fixed at 24 VDC and the panel is built around the S0 frame footprint.
Dimensions: 85 mm height, 45 mm width, 107 mm depth. That depth means it will sit deeper in the enclosure than a compact contactor — account for it when laying out the backplane and gland plate.
Coil and switching performance
The coil is rated 24 V DC, with an initial pickup of 0.8 A and a holding current of 1.1 A at rated value. Dropout time at DC is 15–18 ms; arcing time is 10 ms. Maximum switching frequency varies by duty: 1,000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2 and AC-3 (motor starting/running), and 250 cycles/hour at AC-4 (plugging/inching). The AC-3e rating is also 750 cycles/hour. These limits govern how fast you can cycle the contactor in a process — exceeding them shortens mechanical life.
For auxiliary circuits, the terminals accept 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²). The screw-type terminals are standard for panel builders who prefer screw clamping over spring-cage — no special tooling needed, but torque control matters on the larger wire sizes.