It is a current-production part. Rated for AC-3 duty at 750 operating cycles per hour, this contactor handles motor switching in standard industrial control panels. The 45 mm width and 107 mm depth fit the S0 footprint on 35 mm DIN rail (DIN EN 60715), with snap-on mounting for quick panel integration. Storage range extends to -55 to +80 °C.
These matter for heat dissipation and arc flash containment in dense panels.
Auxiliary switch terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded. Coil terminals are screw-type. DC dropout time is 15 to 18 ms; arcing time is 10 ms.
Maximum operating frequency varies by duty: AC-1 (resistive) at 1000 cycles/h, AC-2 and AC-3 (motor starting/running) at 750 cycles/h, AC-4 (plugging/inching) at 250 cycles/h. AC-3e rating also 750 cycles/h. Auxiliary contact ratings: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V.