The contactor is rated for 3 hp at 230 V and carries DC switching capability up to 10 A at 24 V, 2 A at 48 V, and 0.3 A at 220 V — useful for DC motor brake or solenoid loads in mixed-voltage cabinets.
Duty-cycle and switching frequency
Maximum switching frequency depends on the load duty: 1 000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting/running), 250/h at AC-4 (plugging/inching), and 750/h at AC-3e. For a conveyor or pump running continuous motor duty, the 750/h ceiling is the practical limit; the 250/h AC-4 ceiling matters only if the contactor sees frequent reversing or jogging.
Wiring and auxiliary contacts
Auxiliary switch terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²).