SIRIUS 3RT2026-1NF30 — Size S0 Power Contactor, 95-130 V Coil
The coil is rated for 95-130 V AC, with an inrush current peak of 15 A at pickup.
Envelope and Mounting
These clearances matter for heat dissipation and arc flash containment in a crowded panel — the 10 mm forward clearance is the one most often overlooked when gland plates or busbars are close.
Maximum switching frequency varies by duty class: 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting/running), and 250/h at AC-4 (plugging/inching). The AC-3e rating also caps at 750/h. These limits are thermal — exceeding them will overheat the contact tips, especially under AC-4 duty where the arc is struck at full load each time.