It carries a rated control supply voltage of 200 to 280 VAC and includes an integrated auxiliary switch, eliminating the need for a separate add-on block in many applications.
The Size S0 footprint (45 mm wide, 85 mm high, 107 mm deep) fits standard panel layouts.
Switching Performance and Duty Cycles
Switching times (closing and opening) are 30 to 50 ms for both AC and DC control circuits. Arcing time is a tight 10 ms. Maximum switching frequency varies by duty class: 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting/running), and 250/h at AC-4 (plugging/inching). The AC-3e rating also sits at 750/h. Inrush current peak is 25 A, which the coil circuit must support.
Termination and Wiring
Auxiliary contact terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded. The coil uses screw-type terminals.