Specifications

3RT2026-1NP30-ZX95 — Identification
ParameterValue
Contactor frame sizeS0
3RT2026-1NP30-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V3 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2026-1NP30-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.51
Rated value @ 50 Hz200 ... 280 V
3RT2026-1NP30-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2026-1NP30-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2026-1NP30-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid1 ... 10 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2026-1NP30-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2026-1NP30-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2026-1NP30-ZX95 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth107 mm
3RT2026-1NP30-ZX95 — Specifications
ParameterValue
At AC30 ... 50 ms

Product details

The coil draws an inrush peak of 25 A, so verify your control transformer sizing — that's the instant the contactor pulls in, not the hold-in current.

Mounting & Integration

The S0 frame keeps width to 45 mm, depth 107 mm, height 85 mm. Stranded or solid wire from 1 to 10 mm² on the main contacts.

Switching Performance & Duty

Rated for AC-3 duty (motor switching) at up to 750 operations per hour; AC-4 (plugging/inching) at 250 ops/h. Arcing time is a tight 10 ms, and the coil operates across 200 … 280 V AC. Ambient range during operation is -25 … +60 °C; storage from -55 … +80 °C. The auxiliary switch is built in — no separate add-on needed for feedback or status indication.

Frequently asked questions

Where can I buy 3RT2026-1NP30-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the coil voltage range for 3RT2026-1NP30-ZX95?

The coil is rated 200 … 280 V AC. Inrush peak is 25 A at pull-in.

What are the mounting dimensions and clearances for 3RT2026-1NP30-ZX95?

Width 45 mm, height 85 mm, depth 107 mm. Clearances: 10 mm upwards, forwards, and downwards; 6 mm at the side. Mounts on 35 mm DIN rail per DIN EN 60715.