Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, fitting into a compact 45 mm wide by 102 mm tall by 144 mm deep footprint — useful when panel space is tight.
Rated for AC-1 resistive loads at up to 1,000 switching cycles per hour, AC-2 and AC-3 motor loads at 750 cycles/h, and AC-4 (plugging/inching) at 250 cycles/h — so the duty cycle governs how often this contactor can break motor current without overheating. The coil draws 6 A at 24 V rated value, dropping to 2 A at 48 V and 0.3 A at 220 V — important for sizing the control transformer and verifying the DC supply can handle the inrush. Main contact wire range accepts solid or stranded conductors from 1 to 10 mm², with auxiliary contacts taking 2x (0.5 to 2.5 mm²) — covers most panel wiring without needing oversized lugs.
Requires 10 mm clearance upward, downward, and forward, plus 6 mm at the sides — plan your DIN rail layout so adjacent devices don't block ventilation or arc paths.
Listed as current production.