It mounts via screw or snap-on onto 35 mm standard mounting rail per DIN EN 60715, with a ±180° rotation possible on a vertical surface and ±22.5° tilt forward/backward. The auxiliary contact block carries 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.6 A at 440 V — covering a wide control-voltage range for mixed-voltage panels.
The contactor body measures 45 mm wide, 102 mm high, and 97 mm deep. These clearances govern panel layout density — stacking contactors without the 6 mm side gap may cause thermal derating or arc-flash bridging. Wire range: solid or stranded 1–10 mm² for the main circuit, with 2x (0.5–2.5 mm²) for auxiliary connections. Spring-clamp terminals accept ferruled stranded; strip length and ferrule size follow the terminal manufacturer's spec for reliable pull-out force.
Operating Duty and Thermal Limits
Maximum switching frequency: 1,000 cycles/h at AC-1, 750 cycles/h at AC-2 and AC-3, 750 cycles/h at AC-3e, and 250 cycles/h at AC-4. Arcing time at AC is 4–16 ms, with a rated arcing time of 10 ms.