Skip to main content
Siemens 3RT2026-2AP04-ZX95 — Contactors

Siemens SIRIUS 3RT2026-2AP04-ZX95 Power Contactor, S0, Sprin

MPN3RT2026-2AP04-ZX95
Active

Siemens SIRIUS, power contactor, 3RT2026-2AP04-ZX95, size S0, spring-type terminals on magnet coil, screw and snap-on mounting onto 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2026-2AP04-ZX95 — Identification
ParameterValue
Contactor frame sizeS0
3RT2026-2AP04-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V3 hp
Rated value @ 24 V6 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2026-2AP04-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT2026-2AP04-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2026-2AP04-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2026-2AP04-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid1 ... 10 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2026-2AP04-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2026-2AP04-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2026-2AP04-ZX95 — Mechanical
ParameterValue
Width45 mm
Height102 mm
Depth144 mm
3RT2026-2AP04-ZX95 — Specifications
ParameterValue
At AC4 ... 16 ms

Product details

At 480 V, the AC-3 rating is 21 A — that's the motor-switching current it handles for standard squirrel-cage motors, so a typical 10 hp motor at 480 V is well within range. The magnet coil uses spring-type terminals, not screw clamps — that means faster wiring in the panel and no risk of screw loosening under vibration. There is no built-in auxiliary switch block on this variant, so if you need feedback contacts for a PLC or status lamp, you'll add a separate auxiliary contactor block.

Frequently asked questions

What are the key dimensions of this contactor?

The contactor measures 45 mm wide, 102 mm high, and 144 mm deep, which is the standard S0 footprint.

What wire sizes does the main circuit accept?

The main circuit terminals accept solid or stranded conductors from 1 to 10 mm², and two conductors of 0.5 to 2.5 mm² can be paralleled into one terminal.

MPN
3RT2026-2AP04-ZX95