At 480 V, the AC-3 rating is 21 A — that's the motor-switching current it handles for standard squirrel-cage motors, so a typical 10 hp motor at 480 V is well within range. The magnet coil uses spring-type terminals, not screw clamps — that means faster wiring in the panel and no risk of screw loosening under vibration. There is no built-in auxiliary switch block on this variant, so if you need feedback contacts for a PLC or status lamp, you'll add a separate auxiliary contactor block.

Siemens SIRIUS 3RT2026-2AP04-ZX95 Power Contactor, S0, Sprin
MPN3RT2026-2AP04-ZX95
Active
Siemens SIRIUS, power contactor, 3RT2026-2AP04-ZX95, size S0, spring-type terminals on magnet coil, screw and snap-on mounting onto 35 mm DIN rail.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S0 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 15.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 3 hp |
| Rated value @ 24 V | 6 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC |
| Rated value @ 50 Hz | 0.25 |
| Rated value @ 50 Hz | 230 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 kA) |
| Short-circuit coordination type 2, fuse | gG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V, 80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | spring-loaded terminals |
| Aux. / control circuit connection | spring-loaded terminals |
| Conductor cross-section, solid | 1 ... 10 mm² |
| Conductor cross-section, solid or stranded | 2x (0.5 ... 2.5 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 1.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 10 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 102 mm |
| Depth | 144 mm |
| Parameter | Value |
|---|---|
| At AC | 4 ... 16 ms |
Product details
Frequently asked questions
What are the key dimensions of this contactor?
The contactor measures 45 mm wide, 102 mm high, and 144 mm deep, which is the standard S0 footprint.
What wire sizes does the main circuit accept?
The main circuit terminals accept solid or stranded conductors from 1 to 10 mm², and two conductors of 0.5 to 2.5 mm² can be paralleled into one terminal.
MPN