It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward/backward — useful when fitting into tight gland-plate layouts or existing busbar arrangements.
The 24 V DC coil pulls 6 A at rated voltage, with a pickup dropout range of 0.8 to 1.1 times the rated value — so the coil holds reliably down to about 19.2 V and drops out below 18 V. AC-4 duty (plugging/inching) is limited to 250 ops/h. No built-in auxiliary switch, so if you need N.O./N.C. feedback for a PLC or safety circuit, you'll add a side-mount block. The main contact wire range accepts solid or stranded 1–10 mm², with a separate pair of terminals for 2x (0.5–2.5 mm²) — enough for the coil and auxiliary wiring without doubling up on the power terminals.