3RT2026-2CL24-3MA0 — Identification
ParameterValue
Contactor frame sizeS0
3RT2026-2CL24-3MA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V3 hp
Rated value @ 24 V6 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2026-2CL24-3MA0 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT2026-2CL24-3MA0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2026-2CL24-3MA0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2026-2CL24-3MA0 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid1 ... 10 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2026-2CL24-3MA0 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2026-2CL24-3MA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2026-2CL24-3MA0 — Mechanical
ParameterValue
Width45 mm
Height102 mm
Depth144 mm
3RT2026-2CL24-3MA0 — Specifications
ParameterValue
At AC4 ... 16 ms

Product details

At 45 mm wide, 102 mm tall, and 144 mm deep, this S0 contactor fits standard panel layouts and leaves room for adjacent devices on the DIN rail.

Switching frequency and duty ratings

The contactor is rated for 1,000 switching cycles per hour in AC-1 resistive load duty, 750 cycles/h in AC-2 and AC-3 motor duty, and 250 cycles/h in the demanding AC-4 plugging/reversing duty. These numbers define the thermal limit of the contactor under load — exceeding them shortens mechanical life or risks contact welding.

Wiring and conductor sizing

Main power terminals accept solid or stranded conductors from 1 to 10 mm², and the auxiliary/coil terminals accept 2x (0.5 to 2.5 mm²) solid or stranded wire. The spring-type coil terminals eliminate the need for screwdriver torque checks during panel build. These minimum air gaps must be maintained for proper heat dissipation and arc quenching.

Environmental range and mounting flexibility

Frequently asked questions

What are the key dimensions for panel layout?

The contactor measures 45 mm wide, 102 mm tall, and 144 mm deep. It requires 10 mm clearance upwards, downwards, and forwards, plus 6 mm at the sides for proper ventilation and arc containment.

What wire sizes does this contactor accept?

Main power terminals accept 1 to 10 mm² solid or stranded conductors. The coil terminals accept 2x (0.5 to 2.5 mm²) solid or stranded wire via spring-type terminals.

What switching frequencies can this contactor handle?

Rated for 1,000 cycles/h in AC-1 resistive duty, 750 cycles/h in AC-2 and AC-3 motor duty, and 250 cycles/h in AC-4 plugging/reversing duty. Mechanical life is rated at 10 million cycles typical.