What It Is & Where It Goes
The 24 VAC 50/60 Hz coil draws 0.25 A at 50 Hz and 0.28 A at 60 Hz — a standard control voltage that matches most PLC or relay outputs in European and North American panels.
The 45 mm width and 85 mm height fit standard S0 contactor spacing in a panel.
Switching Performance & Duty Cycles
Rated for 1 000 000 electrical operations typical. Maximum switching frequency varies by duty: 1 000 cycles/hour for AC-1 (resistive), 750 cycles/hour for AC-2 and AC-3 (motor starting/running), and 250 cycles/hour for AC-4 (plugging/inching). Arcing time is 10 ms. For a bottling line or conveyor running at moderate start frequency, the AC-3 rating of 750 cycles/hour is the relevant limit — it means the contactor can handle a start every ~5 seconds without overheating the arc chamber.
Auxiliary & Main Contact Configuration
Includes an auxiliary switch block. Main contacts accept wire sizes 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). The S0 frame matches the 3RT2027-1AP60 for mechanical fit.