Motor switching capability at 480 V
The AC-3 rating governs motor starting and running — the contactor must interrupt locked-rotor current during starting, and 27 A at 480 V gives a solid margin for a 15 hp motor at that voltage.
Integration notes
Screw-type terminals for the magnet coil and main contacts accept solid or stranded wire from 1 to 10 mm², with dual-wire capability for 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). Minimum clearance at the side is 6 mm; upward, downward, and forward clearance is 10 mm.