The contactor mounts via screw or snap-on onto 35 mm DIN rail per EN 60715, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt — useful when fitting into tight panel layouts.
Ratings and operating envelope
The main contact rating is 18...8 A (likely the thermal continuous current range at lower voltages), while the headline AC-3 motor-switching current at 480 V is 27 A. The coil is rated for 24 VDC at 10 A (holding current), with lower currents at higher control voltages: 2 A at 48 V, 1 A at 110 V, 0.3 A at 220 V.
No successor or phase-out date is recorded.
The contactor measures 45 mm wide, 102 mm high, and 97 mm deep. That depth is the body depth; add clearance for wiring and arc chutes. The spring-type terminals accept solid or stranded wire from 1 to 10 mm², and dual-wire entry (2x 0.5...2.5 mm²) is supported. These numbers matter when laying out DIN-rail spacing to avoid shorting between phases or to adjacent components.