The main contacts are rated for AC-3 switching at up to 750 operating cycles per hour, with AC-4 limited to 250 cycles/h. An auxiliary switch is built in, rated for 10 A at 24 V DC, derating to 0.3 A at 220 V DC.
Dimensions are 102 mm high, 45 mm wide, 107 mm deep — the standard S0 footprint.
Wiring practice note
Main contact terminals accept solid conductors 2x (1... 10 mm²) or stranded 2x (0.5... 2.5 mm²). The coil uses spring-type terminals — no screw torque to verify, but ensure the stripped length is correct for the cage clamp. Inrush current peak is 3 A at 24 V DC coil pickup. Arcing time is 10... 10 ms; for DC switching, the arc extinguishes in 30... 50 ms.