Skip to main content
Siemens 3RT2027-4AP60 — Contactors

Siemens SIRIUS 3RT2027-4AP60 Power Contactor, S0, 27 A at 48

MPN3RT2027-4AP60

Siemens SIRIUS 3RT2027-4AP60 power contactor, size S0, 27 A at 480 V, 5 hp at 230 V, screw and snap-on 35 mm DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2027-4AP60 — Identification
ParameterValue
Contactor frame sizeS0
3RT2027-4AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V22 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V5 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2027-4AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz220 V
3RT2027-4AP60 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2027-4AP60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 125A (690V,100kA), aM: 50A (690V,100kA), BS88: 125A (415V,80kA)
Short-circuit coordination type 2, fusegG: 50A (690V,100kA), aM: 25A (690V, 100kA), BS88: 50A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2027-4AP60 — Connection & Mounting
ParameterValue
Main circuit connectionRing cable lug connection
Aux. / control circuit connectionring terminal lug connection
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2027-4AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2027-4AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2027-4AP60 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth97 mm
3RT2027-4AP60 — Specifications
ParameterValue
At AC4 ... 16 ms

Product details

It carries a 27 A rated operational current at 480 V and a 5 hp rating at 230 V, which tells you it can handle a 5 hp motor on a 230 V single-phase or three-phase line, or a 27 A resistive load at 480 V.

Switching frequency and thermal limits

Rated for up to 1 000 operations per hour in AC-1 resistive duty, and 750 ops/h in AC-3 motor switching. That's enough for most conveyor and pump cycling — if you're pushing AC-4 reversing or inching duty, it drops to 250 ops/h, so plan your cycle count accordingly.

Frequently asked questions

What are the key dimensions for panel layout?

Width is 45 mm, height 85 mm, depth 97 mm. It mounts on 35 mm DIN rail per DIN EN 60715.

What is the motor rating at 230 V?

It is rated at 5 hp at 230 V, which covers a typical 5 hp motor on a 230 V single-phase or three-phase supply.

Does it include an auxiliary contact?

Yes, it has an integrated auxiliary switch, so you don't need a separate add-on for basic feedback or interlocking.

MPN
3RT2027-4AP60